| Parameter | JUPITER-9000K-H1 | JUPITER-6000K-H1 | JUPITER-3000K-H1 |
|---|---|---|---|
| Input | |||
| Available Inverters / PCS | SUN2000-330KTL-H1 / SUN2000-330KTL-H2 / LUNA2000-200KTL-H1 | ||
| Max. LV AC Inputs | 30 | 22 | 11 |
| AC Power | 9,000 kVA @40°C1 | 6,600 kVA @40°C1 | 3,300 kVA @40°C1 |
| Rated Input Voltage | 800 V | ||
| LV Panel Segregation | Form 2b | ||
| LV Main Switches (ACB) | 4,000 A, 2 × 1 pcs | 2,900 A, 2 × 1 pcs | 2,900 A, 1 × 1 pcs |
| LV Main Switches for Inverters / PCS (MCCB) | 400 A, 2 × 15 pcs | 400 A, 2 × 11 pcs | 400 A, 11 pcs |
| Output | |||
| Rated Output Voltage | 10~35 kV2 | ||
| Frequency | 50 Hz or 60 Hz | ||
| Transformer Type | Oil-immersed, Conservator Type | ||
| Transformer Cooling Type | ONAN | ||
| Transformer Tappings | ± 2 × 2.5% | ||
| Transformer Oil Type | Mineral Oil (PCB Free) | ||
| Transformer Vector Group | Dy11-y11 | Dy11 | |
| Transformer Min. Peak Efficiency Index | Tier 1 or Tier 2 In Accordance with EN 50588-1 | ||
| RMU Type | SF₆ Gas Insulated | ||
| RMU Transformer Protection Unit | MV Vacuum Circuit Breaker Unit | ||
| RMU Cable Incoming / Outgoing Unit | Direct Cable Unit or Cable Load Break Switch Unit | ||
| Auxiliary Transformer | Dry Type Transformer, 5 kVA, Single-phase, li0 | ||
| Output Voltage of Auxiliary Transformer | 230 / 127 Vac | ||
| Protection | |||
| Transformer Detection & Protection | Oil Level, Oil Temperature, Oil Pressure and Buchholz | ||
| Protection Degree of MV & LV Room | IP 54 | ||
| Internal Arcing Fault of STS | IAC A 20 kA 1s | ||
| MV Relay Protection | 50/51, 50N/51N | ||
| LV Overvoltage Protection | Type I+II | ||
| Anti-rodent Protection | C5-Medium | ||
| Features | |||
| 2 kVA UPS | Optional3 | ||
| MV Surge Arrester for Transformer | Optional3 | ||
| General | |||
| Dimensions (W × H × D) | 6,058 × 2,896 × 2,438 mm (20' HC ISO Container) | ||
| Weight | < 28 t | < 23 t | < 15 t |
| Operating Temperature Range | -25°C ~ 60°C4 | ||
| Relative Humidity | 0% ~ 95% (Non-condensing) | ||
| Max. Operating Altitude | 1,000 m5 | ||
| MV-LV AC Connections | Prewired and Pretested, No Internal Cabling Onsite | ||
| LV & MV Room Cooling | Smart Cooling without Air-across for Higher Availability | ||
| Communication | Modbus TCP, Preconfigured with SmartACU2000D | ||
| Standards Compliance | |||
| Certifications | IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1, etc. | ||
1. More detailed AC power of STS, please refer to the de-rating curve.
2. Rated output voltage from 10 kV to 35 kV, more available upon request.
3. Extra expense needed for optional features which standard product doesn't contain, more options upon request.
4. When ambient temperature ≥55°C, awning shall be equipped for STS on site by customer.
5. For higher operating altitude, pls consult with Huawei.