| Parameter | JUPITER-9000K-H1 (Built-in SACU) | JUPITER-6000K-H1 (Built-in SACU) | JUPITER-3000K-H1 (Built-in SACU) |
|---|---|---|---|
| Input | |||
| Available Inverters / PCS | SUN2000-330KTL-H1 / SUN2000-330KTL-H2 / LUNA2000-213KTL-H0 | ||
| Max. MCCB inputs | 30 | 22 | 121/11 |
| Max. LV AC Inputs | 602 | 442 | 242/12 |
| AC Power | 9,000 kVA @40°C3 | 6,600 kVA @40°C3 | 3,300 kVA @40°C3 |
| Rated Input Voltage | 800 V | ||
| LV Panel Segregation | Form 2b | ||
| LV Main Switches | ACB (4,000 A, 2 x 1 pcs) MCCB (400 A, 2 x 15 pcs)4 | ACB (2,900 A, 2 x 1 pcs) MCCB (400 A, 2 x 11 pcs)4 | ACB (2,900 A, 1 x 1 pcs) MCCB (400 A, 11 pcs)4 |
| Output | |||
| Rated Output Voltage | 10~35 kV4 | ||
| Frequency | 50 Hz or 60 Hz | ||
| Transformer Type | Oil-immersed, Conservator Type | ||
| Transformer Cooling Type | Mineral Oil: ONAN / Natural Ester: KNAN | ||
| Transformer Tappings | ± 2 × 2.5% | ||
| Transformer Oil Type | Mineral Oil (PCB Free)/Natural ester oil (Optional) | ||
| Transformer Vector Group | Dy11-y11 | Dy11 | |
| Transformer Min. Peak Efficiency Index | Tier 1 or Tier 2 In Accordance with EN 50588-1 | ||
| RMU Type | SF₆ Gas Insulated | ||
| RMU Transformer Protection Unit | MV Vacuum Circuit Breaker Unit | ||
| RMU Cable Incoming / Outgoing Unit | Direct Cable Unit or Cable Load Break Switch Unit | ||
| Auxiliary Transformer | Dry Type Transformer, 5 kVA, Single-phase, li0/50kVA, Three-phase, Dyn11 (Optional) | ||
| Output Voltage of Auxiliary Transformer | 400/230/220/210V | ||
| Protection | |||
| Transformer Detection & Protection | Oil Level, Oil Temperature, Oil Pressure and Buchholz | ||
| Protection Degree of MV & LV Room | IP 54 | ||
| Internal Arcing Fault of STS | Standard IAC A 20 kA 1s/ IAC A 25 kA 1s (Optional) | ||
| MV Arc Releasing | MV Upward Arc Releasing for Higher Safety, Meets IEC 62271-202 IAC-A | ||
| LV Arc Releasing | Meets IEC 61641 up to Class C arcing protection on LV side | ||
| MV Relay Protection | DVC/CVC Standard 50/51, 50N/51N DVC/CVC High Standard adds 87, 50BF, Inrush Blocking, Watchdog, 49T (External trip), FR (Optional) | ||
| LV Overvoltage Protection | Type I+II | ||
| Anti-corrosion Protection | C5-M | ||
| Feature | |||
| 2 kVA UPS | Optional5 | ||
| MV Surge Arrester for Transformer | Optional5 | ||
| IMD License | Optional5 | ||
| General | |||
| Dimensions (W × H × D) | 6,058 × 2,896 × 2,438 mm (20' HC ISO Container) | ||
| Weight | < 28 t | < 23 t | < 17 t |
| Operating Temperature Range | -25°C ~ 60°C6 | ||
| Relative Humidity | 0% ~ 95% (Non-condensing) | ||
| Max. Operating Altitude | 1,000 m7 | ||
| MV-LV AC Connections | Prewired and Pretested, No Internal Cabling Onsite | ||
| LV Room Cooling | Smart Cooling without Air-across for Higher Availability | ||
| Communication | Modbus TCP, Preconfigured with SmartACU | ||
| Standards Compliance | |||
| Certifications | IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1, etc. | ||
1. only for GFM version
2. one MCCB can aggregate one inverter and one PCS at the same time, Max. LV AC Inputs means Theoretical number of full-access PCS
3. More detailed AC power of STS, please refer to the de-rating curve.
4. Rated output voltage from 10 kV to 35 kV, more available upon request
5. Extra expense needed for optional features which standard product doesn't contain, more options upon request.
6. When ambient temperature ≥55°C, awning shall be equipped for STS on site by customer.
7. For higher operating altitude, please consult with Huawei.