| Parameter | GW50KS-MT | GW60KS-MT |
|---|---|---|
| Input | ||
| Max. Input Voltage (V) | 1100 | |
| MPPT Operating Voltage Range (V) | 200 ~ 950 | |
| Start-up Voltage (V) | 180 | |
| Nominal Input Voltage (V) | 600 | |
| Max. Input Current per MPPT (A) | 30 | |
| Max. Short Circuit Current per MPPT (A) | 37.5 | |
| Number of MPPT Trackers | 5 | 6 |
| Number of Strings per MPPT | 2 | |
| Output | ||
| Nominal Output Power (kW) | 50 | 60 |
| Nominal Output Apparent Power (kVA) | 50 | 60 |
| Max. AC Active Power (kW) | 55¹ | 66¹ |
| Max. AC Apparent Power (kVA) | 55² | 66² |
| Nominal Output Voltage (V) | 230 / 400³, 3L / N / PE or 3L / PE | |
| Output Voltage Range (V) | 320 ~ 460 | |
| Nominal AC Grid Frequency (Hz) | 50 / 60 | |
| AC Grid Frequency Range (Hz) | 45 ~ 55 / 55 ~ 65 | |
| Max. Output Current (A) | 80.0 | 96.0 |
| Output Power Factor | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | |
| Max. Total Harmonic Distortion | <3% | |
| Efficiency | ||
| Max. Efficiency | 98.6% | |
| European Efficiency | 98.1% | |
| Protection | ||
| PV String Current Monitoring | Integrated | |
| PV Insulation Resistance Detection | Integrated | |
| Residual Current Monitoring | Integrated | |
| PV Reverse Polarity Protection | Integrated | |
| Anti-islanding Protection | Integrated | |
| AC Overcurrent Protection | Integrated | |
| AC Short Circuit Protection | Integrated | |
| AC Overvoltage Protection | Integrated | |
| DC Switch | Integrated⁴ | |
| DC Surge Protection | Type II (Type I + II Optional) | |
| AC Surge Protection | Type II | |
| AFCI | Optional | |
| Emergency Power Off⁵ | Optional | |
| Remote Shutdown⁶ | Optional | |
| PID Recovery | Optional | |
| General Data | ||
| Operating Temperature Range (°C) | -30 ~ +60 | |
| Relative Humidity | 0 ~ 100% | |
| Max. Operating Altitude (m) | 3000 | |
| Cooling Method | Smart Fan Cooling | |
| User Interface | LED, LCD (Optional), WLAN + APP | |
| Communication | RS485, WiFi or 4G or PLC (Optional)⁷ | |
| Communication Protocols | Modbus-RTU (SunSpec Compliant) | |
| Weight (kg) | 55 | |
| Dimension (W × H × D mm) | 520 × 660 × 220 | |
| Topology | Non-isolated | |
| Self-consumption at Night (W) | <1 | |
| Ingress Protection Rating | IP65 | |
| DC Connector | MC4 (4 ~ 6mm²) | |
| AC Connector | OT / DT Terminal (Max. 50mm²) | |
¹: For Brazil, Chile and Sri Lanka, Max. AC Active Power (kW): GW50KS-MT is 50; GW60KS-MT is 60.
²: For Brazil, Chile and Sri Lanka, Max. AC Apparent Power (kVA): GW50KS-MT is 50; GW60KS-MT is 60.
³: For Brazil and Thailand (PEA) Nominal Output Voltage (V): 220 / 380, 3L / N / PE or 3L / PE.
⁴: For Australia DC Switch is PV2.
⁵: For Indian Emergency Power Off: Optional.
⁶: For Europe Remote Shutdown: integrated.
⁷: For Brazil Communication is RS485, WiFi, USB, PLC (Optional).
Or contact us immediately:
Call Now