| Models | 12K | 15K | 20K |
|---|---|---|---|
| Input DC (PV side) | |||
| Recommended max. PV array size | 24 kW | 30 kW | 40 kW |
| Max. usable PV input power | 19.2 kW | 24 kW | 32 kW |
| Max. input voltage | 1000 V | ||
| Rated voltage | 600 V | ||
| Start-up voltage | 160 V | ||
| MPPT voltage range | 200 - 850 V | ||
| Max. input current | 4 × 20 A | ||
| Max. short circuit current | 4 × 30 A | ||
| MPPT number / Max. input strings number | 4 / 4 | ||
| Battery | |||
| Battery type | Li-ion | ||
| Battery voltage range | 120 - 800 V | ||
| Max. charge / discharge power | 12 kW | 15 kW | 20 kW |
| Max. charge / discharge current | 50 A | ||
| Communication | CAN / RS485 | ||
| Output AC (Grid side) | |||
| Rated output power | 12 kW | 15 kW | 20 kW |
| Max. apparent output power | 12 kVA | 15 kVA | 20 kVA |
| Rated grid voltage | 3/N/PE,220 V / 380 V,230 V / 400 V | ||
| Rated grid frequency | 50 Hz / 60 Hz | ||
| Rated grid output current | 18.2 A / 17.3 A | 22.8 A / 21.7 A | 30.4 A / 28.9 A |
| Max. output current | 18.2 A / 17.3 A | 22.8 A / 21.7 A | 30.4 A / 28.9 A |
| Power factor | > 0.99 (0.8 leading - 0.8 lagging) | ||
| THDi | < 3% | ||
| Input AC (Grid side) | |||
| Input voltage range | 304 - 437 V / 320 - 460 V | ||
| Max. input current | 27.3 A / 26.0 A | 34.2 A / 32.5 A | 45.6 A / 43.3 A |
| Rated grid frequency | 50 Hz / 60 Hz | ||
| Frequency range | 45 - 55 Hz / 55 - 65 Hz | ||
| Input Generator | |||
| Max. input power | 12 kW | 15 kW | 20 kW |
| Rated input current | 18.2 A / 17.3 A | 22.8 A / 21.7 A | 30.4 A / 28.9 A |
| Rated input frequency | 50 Hz / 60 Hz | ||
| Output AC (Back-up) | |||
| Rated output power | 12 kW | 15 kW | 20 kW |
| Max. apparent output power | 1.6 time of rated power, 10 s | ||
| Back-up switch time | < 10 ms | ||
| Rated output voltage | 3/N/PE,220 V / 380 V,230 V / 400 V | ||
| Rated frequency | 50 Hz / 60 Hz | ||
| Rated output current | 18.2 A / 17.3 A | 22.8 A / 21.7 A | 30.4 A / 28.9 A |
| THDv(@linear load) | < 3% | ||
| Efficiency | |||
| Max. efficiency | 97.7% | ||
| EU efficiency | 97.5% | ||
| BAT charged by PV max. efficiency | 98.5% | ||
| BAT charged / discharged to AC max. efficiency | 97.2% | ||
| Protection | |||
| Anti-islanding protection | Yes | ||
| Output over current protection | Yes | ||
| Short circuit protection | Yes | ||
| Integrated AFCI 2.0 | Optional | ||
| Integrated DC switch | Yes | ||
| DC reverse-polarity protection | Yes | ||
| PV over voltage protection | Yes | ||
| Battery reverse protection | Yes | ||
| General Data | |||
| Max. allowable phase imbalance (grid & back-up) | 100% | ||
| Max. power per phase (grid & back-up) | 40% rated power | ||
| Dimensions (W × H × D) | 563 × 546 × 235 mm | ||
| Weight | 32.6 kg | ||
| Topology | Transformerless | ||
| Self-consumption (night) | < 25 W | ||
| Operating ambient temperature range | -25 ~ +60℃ | ||
| Relative humidity | 0 - 100% | ||
| Ingress protection | IP66 | ||
| Noise emission (typical) | < 65 dB(A) | ||
| Cooling concept | Intelligent fan-cooling | ||
| Max. operation altitude | 4000 m | ||
| Grid connection standard | EN 50549-1/-10, VDE4105, CEI 0-21, NC-RFG TypeB, NRS 097-2-1, LTU-1, G99, PEA | ||
| Safety / EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4 | ||
| Features | |||
| PV connection | MC4 connector | ||
| Battery connection | OT terminal | ||
| AC connection | OT terminal | ||
| Display | LED indicator & Bluetooth + APP | ||
| Communication | CAN, RS485, Ethernet, Optional: Wi-Fi, Cellular, LAN | ||
Or contact us immediately: