| Datasheet | WIT 63K-XHU | WIT 75K-XHU | WIT 85K-XHU | WIT 100K-XHU | WIT 125K-XHU |
|---|---|---|---|---|---|
| Input Data (PV) | |||||
| Max. recommended PV power (for module STC) | 126kW | 150kW | 170kW | 200kW | 250kW |
| Start voltage | 195V | ||||
| Max. open circuit voltage of PV | 1000V | ||||
| MPPT nominal voltage/range | 180V–1000V | ||||
| Max. input current per MPP tracker | 42A | ||||
| Max. short-circuit current per MPP tracker | 50A | ||||
| No. of PV strings per MPP tracker | 2 | ||||
| No. of MPP trackers | 10 | ||||
| Output Data (AC) | |||||
| AC nominal power | 63kW | 75kW | 85kW | 100kW | 125kW |
| Max. AC apparent power | 69.3kVA | 82.5kVA | 93.5kVA | 110kVA | 137.5kVA |
| Nominal AC voltage/range | 380/400/415V, -15%~+10% | ||||
| AC grid frequency/range | 50/60Hz, 45–55Hz/55–65Hz | ||||
| Max. output current | 105A | 125A | 141.7A | 166.7A | 208.3A |
| Adjustable power factor | -1…+1 | ||||
| THDi | <3%(@100% load) | ||||
| AC grid connection type | 3P3W+PE/3P4W+PE | ||||
| Input Data (AC/GEN) | |||||
| Nominal AC voltage/range | 380/400/415V, -15%~+10% | ||||
| Nominal AC grid frequency/range | 50/60Hz, 45–55Hz/55–65Hz | ||||
| AC grid connection type | 3P3W+PE/3P4W+PE | ||||
| Rated input power | 63kW | 75kW | 85kW | 100kW | 125kW |
| Max. input current | 250A | ||||
| Battery Data (DC) | |||||
| Continuous charging and discharging power | 63kW | 75kW | 85kW | 100kW | 125kW |
| Battery voltage range | 180–1000V(900V derating) | ||||
| Max charging and discharging current | 200A | ||||
| BMS communication | RS485/CAN | ||||
| Backup Power (AC) | |||||
| Rated AC output power | 63kW | 75kW | 85kW | 100kW | 125kW |
| Max. AC apparent power | 69.3kVA | 82.5kVA | 93.5kVA | 110kVA | 137.5kVA |
| Nominal AC voltage | 220/230/240V(L-N),380/400/415V(L-L) | ||||
| Nominal AC output frequency | 50/60Hz | ||||
| Load connection | 3P3W+PE/3P4W+PE | ||||
| Max. output current | 105A | 125A | 141.7A | 166.7A | 208.3A |
| THDv | <3%(Linear load) | ||||
| Load unbalance | 100% three-phase unbalanced | ||||
| Overload capacity | ≤110%: Continues; 160%:10s | ||||
| On/Off grid transfer time | <10ms | ||||
| Efficiency | |||||
| Max. efficiency | 98.5% | ||||
| Protection Devices | |||||
| DC reverse polarity protection | Yes | ||||
| Battery reverse protection | Yes | ||||
| AC/DC surge protection | Type II | ||||
| Insulation resistance monitoring | Yes | ||||
| Ground fault monitoring | Yes | ||||
| Grid monitoring | Yes | ||||
| Residual-current monitoring unit | Yes | ||||
| AC short-circuit protection | Yes | ||||
| Strings monitoring | Yes | ||||
| Anti-islanding protection | Yes | ||||
| PID protection | Yes | ||||
| AFCI function | Yes | ||||
| General | |||||
| Dimensions(W/H/D) | 720/1360/400mm | ||||
| Weight | 160kg | ||||
| Operating temperature range | -30℃~60℃,>50℃ derating | ||||
| Relative humidity | 0–100% | ||||
| Altitude | ≤4000m | ||||
| Topology | Transformerless | ||||
| Cooling | Smart air cooling | ||||
| Enclosure | IP66 | ||||
| Display | OLED+LED+WIFI+APP | ||||
| Interfaces: RS485/CAN | Yes | ||||
| Interfaces: WIFI/4G/LAN | Opt | ||||
| Warranty (5/10 years) | Yes/Opt | ||||
| CE/CB, ROHS, IEC62109-1/2, IEC62116, IEC61727, IEC61683, IEC60068, EN50549-1-10, EN50549-2-10, CEI 0-16 & 021, UNE 21700,NTS,NRS097-2-1 | |||||
Or contact us immediately: