WIT 29.9-50K-XHU Three Phase Hybrid

Daran New Energy Technology Co., Ltd is engaged in solar panels, inverters, battery pack production and sales of manufacturers.

Price

24-hour hotline
+8618031297729

Parameter
Datasheet Table
DatasheetWIT 29.9K-XHUWIT 30K-XHUWIT 36K-XHUWIT 40K-XHUWIT 50K-XHU
Input Data (PV)
Max. recommended PV power (for module STC)59.8kW60kW72kW80kW100kW
Start voltage195V
Max. DC voltage1100V
Nominal voltage620V
Max. open circuit voltage of PV1000V
Operating voltage range180V–1000V
Full load DC voltage range375V–850V375V–850V450V–850V500V–850V620V–850V
Max. input current per MPP tracker40A
Max. short-circuit current per MPP tracker50A
No. of PV strings per MPP tracker2
No. of MPP trackers4
Battery Data (DC)
Battery voltage range200–800V200–800V200–900V250–800V310–800V
Full load battery voltage range225–800V
Recommended battery voltage512V
No. of battery input3
Max. charging/discharging current55A*3
BMS communicationRS485/CAN
Input/Output AC
AC input/output nominal power(Grid)59.8kW/29.9kW60kW/30kW72kW/36kW80kW/40kW100kW/50kW
Max. AC input/output apparent power⁴59.8kVA/29.9kVA66kVA/33kVA79.2kVA/39.6kVA88kVA/44kVA110kVA/55kVA
Max. input/output current(Grid)90.6A/45.3A100A/50A120A/60A133.3A/66.7A166.7A/83.3A
Max. input current(GEN/AC couple)90.6A/45.3A100A/45.5A120A/65.4A133.3A/60.7A166.7A/75.7A
Max. continuous AC passthrough current200A
Nominal AC voltage/range380/400V -15%~+10%
Nominal AC grid frequency/range50Hz/60Hz,45–55Hz/55–65Hz
Power factor(@nominal power)>0.99
Adjustable power factor-1 ~ +1
THDi<3%
AC grid connection type3P3W+PE/3P4W+PE
Backup Power
AC nominal output power29.9kW30kW36kW40kW50kW
Max. AC apparent power29.9kVA45kVA54kVA60kVA75kVA
Nominal AC voltage220V/230V(L-N),380V/400V(L-L)
Nominal AC frequency50/60Hz
Max. output current68.0A68.2A81.8A91A113.6A
Overload capability1.5 times of rated power, 10s
THDv<3%(@Linear full load)
Switch time≤10ms
Efficiency
Max. efficiency98.1%
Protection Devices
DC reverse polarity protectionYes
Battery reverse protectionYes
Insulation resistance monitoringYes
AC/DC surge protectionType II
AC short-circuit protectionYes
Ground fault monitoringYes
Grid monitoringYes
String monitoringYes
Anti-islanding protectionYes
Residual-current monitoring unitYes
General Data
Dimensions (W/H/D)920/585/320mm
Weight90kg
Operating temperature range-30℃ ~ 60℃ (>50℃ derating)
Noise emission≤55dB
Altitude4000m
TopologyTransformerless
CoolingSmart air cooling
Protection degreeIP66
Relative humidity0~95%
Interfaces
DisplayOLED+LED/APP
InterfacesRS485/USB/CAN, WIFI/LAN(Opt)
Warranty: 5 / 10 yearsYes/Opt
CE/CB, ROHS, IEC 62109-1, IEC 62109-2, IEC 62477-1, EN 62920, IEC 61000-4-2, IEC 61000-4-6, IEC 61000-3-12, IEC 61000-3-11, EN 55011, IEC 62116, IEC 61727, IEC 61683, IEC 60068-2-1, NRS097-2-1
*1 The AC voltage range may varying depending on specific country grid standard. All specifications are subject to change without notice.